Lightning impulse (LI) breakdown testing of a rubber-epoxy interface

Cecilia Forssén, Anne Christerson, Daniel Borg

Abstract


The lightning impulse (LI) breakdown strength of a rubber-epoxy interface was measured using a test cell developed earlier for AC breakdown testing. The electrically active length of the rubber-epoxy interface in the test cell was about 10 mm. The rubber was compressed and the pressure in the rubber-epoxy interface was controlled and measured. It was shown that the test cell performed well under LI breakdown testing with the majority of the breakdowns located at the rubber-epoxy interface as desired and not in the bulk insulation. A higher LI breakdown strength was obtained for smoother epoxy surfaces.


Keywords


Lightning impulse; Breakdown; Interface

Full Text:

PDF


DOI: http://dx.doi.org/10.5324/nordis.v0i25.2371